easy-guard - fire upgrade coating - Class "0"
General Specification:
1. Attend site and carry out adhesion tests to pre-painted wall and ceiling surfaces.
2. Identify any areas of weak inter-coat adhesion and scrape back to a hard edge.
3. Feather off as necessary.
4. Thoroughly abrade all glossy/hard surfaces down and degrease with easy-guard Wash Down Agent and rinse with clean water.
5. To clean dry surfaces apply 1 coat of easyguard Class “0” Bond Primer by brush/ roller at a coverage rate of 14-16m²/litre Allow at least 1 hour drying time.
6. Apply 1 coat of easy-guard Class “0” Barrier Compound by brush/roller at a coverage rate of 0.45m2/litre. Pattern as necessary and lace down when hard dry.
7. Apply 1 coat of easy-guard Class “0” Colour Coat by brush/roller at a coverage rate of 6-12 m²/litre. Allow at least 8 hours drying time.
8 Provide Contract Administrator with Fire Test Certificates demonstrating Class “0” performance over the Warrington “Blue” Board in full accordance with the Warrington Application Monitoring Procedure.
|
easy guard - flame resistant paint - Class "1"
General Specification:
1. Attend site and carry out adhesion tests to all pre-painted wall and ceiling surfaces.
2. Identify any areas of weak intercoat adhesion and scrape back to a hard edge.
3. Feather off as necessary and fill using a high quality filling compound.
4. Thoroughly abrade all glossy/hard surfaces. Wash down and degrease with easy-guard Wash Down Agent and rinse with clean water.
5. Spot prime any bare or filled patches with 1 coat of easy-guard Fire Upgrading Primer thinned 10% with clean water.
6. Apply 1 full coat of easy-guard Fire Upgrading Primer by brush/roller at a coverage rate of 8.0m²/litre. Allow 24 hours drying time.
7. Apply 1 full coat of easy-guard Fire Upgrading Colour Coat by brush/ roller at a coverage rate of 8.0m²/ litre. Allow at least 24 hours drying time.
|